Profile: |
| PX24 |
PXN24, PX230 |
 |
 |
| Description |
- designed for DIN 35 rail mounting
- input and output are isolated from each other as well as from supply circuits
- conversion accuracy < 0,2% |
The module has been designed to convert DC current
and voltage from shunt resistors and sensors into a series of unified ranges (0..10V, 0..20mA, 4..20mA).
The converter output-to-input response is linear. The converter is particularly well-suited for heavy
electromagnetic interference environment operation and features input-to-output isolation. |
Electrical specifications: |
| - operating temperature range: |
-25...+70°C |
| - supply voltage: |
12..30V DC, maximum ripple: 0,5V (measured across the device terminals), for PX24 |
| |
24V DC ± 30% for PXN24 |
| |
230V AC ± 10% ( 45 - 65 Hz ) for PXN230 |
| - power input: |
max. 2VA |
| - current limit: |
30mA±5mA |
| - maximum output voltage: |
27V |
| - output voltage amplitude: |
min. 15V (R load = 750W) at 20mA (except PX24) |
| - voltage output load: |
max. 10mA |
| - inputs: |
DC voltages: from 10mV to 500V |
| |
DC currents: from 10µA to 500mA |
| - output: |
0..1V, 0..5V, 0..10V, 0..5mA, 0..20mA, 4..20mA |
| - accuracy: |
measurement error: |
< 0,2% |
| |
linearity error: |
< 0,1% |
| |
temperature induced error: |
< 0,02%/°C |
| - enclosure: |
casing / terminal board: |
IP40 / IP10 |
| - dielectric strength: |
4000Vr.m.s., 50Hz/1 min |
| - settling time: |
300ms |
| |
|
|
| Type tests: |
Standard type test:
EMC:
Safety: |
to CSN EN 60770-1
to CSN EN 61326-1
assessed acc. to CSN EN 61010-1 |
Terminal connection: |
1, 2, 3 ...........
4,5.................
6,7................. |
input (3 is +)
output (5 is +)
24V DC power supply terminals (7 is +), or 230V AC, depending on the type
they are not connected in PX24, the converter is powered via its output line |
| The terminals accept wires with cross sections not exceeding 2,5mm2. |
Converter dimensions:
|
| |
|
Kinds of connection:
|
| |
|
Ordering instructions:
The device has a fixed factory setting. The input signal
type and range cannot be changed. The output setting is fixed, too. The output type of PX24 cannot
be selected, it is fixed to 4..20mA. This information must therefore be included in your purchase
order.
Your purchase order should include: converter type, input
signal type and range, output signal type and range, number of pieces. Special requirements must
be discussed with us beforehand.
|
| Examples: |
PX24 0..60mV, 2 pcs.
PXN24 0..500V/4..20mA, 1pc.
PXN230 5..45mA/0..10V, 3pcs. |
|
|