Profile: |
| |
PX210 |
| |
 |
Description: |
| |
- input for DC current, voltage or termocouple
- conversion accuracy < 0.1%
- output signal is standard 4...20 mA.
- input and output are isolated - 4kV
- designed for DIN 35 rail mounting |
Electrical specifications: |
| - operating temperature range: |
-25...+70°C |
| - supply voltage: |
8...28V DC (polarity reversal protection) |
| - output resolution: |
0,025% |
| - input signal: |
termocouple J, T, K, E, N, L, S, R, B,C,D,G
direct voltage by order for instance: 0...1V, 0...10V, 0...300V, max.600V
direct voltage current for instance: 0...20mA, max 2A |
| - accuracy: |
conformity error: |
< 0,1% from range |
| |
temperature effect: |
<0,05%/10K |
| - damping |
0..30s |
| - protection housing / terminal: |
IP40 / IP10 |
| - montage: |
DIN 35 mm rail |
| - leads connection: |
wire 0,5 až 2,5mm2 |
| - custom linearization: |
yes |
| - accessory (optional): |
programmable adaptor PK-USB (with free SW) |
| - dimension: |
see schema |
| |
|
|
| Type of thermocouple |
Range |
Nonlinearity error |
| Fe-Ko |
L |
DIN 43 710 |
-25 .. +900°C |
0,1% |
| Fe-Ko |
J |
EN 60 584 |
-210 .. +1200°C |
0,1% |
| Cu-Ko |
T |
EN 60 584 |
-270 .. +400°C |
0,1% |
| NiCr-Ni |
K |
EN 60 584 |
-270 .. +1372°C |
0,1% |
| NiCr-Ko |
E |
EN 60 584 |
-270 .. +1000°C |
0,1% |
| NiCrSi-NiSi |
N |
EN 60 584 |
-270 .. +1300°C |
0,1% od -130°C |
| Pt10Rh-Pt |
S |
EN 60 584 |
-50 .. +1760°C |
0,15% od 0°C |
| Pt13Rh-Pt |
R |
EN 60 584 |
-50 .. +1767°C |
0,15% od 0°C |
| Pt30Rh-Pt6Rh |
B |
EN 60 584 |
0 .. +1820°C |
0,15% od 400°C |
| W3Re-W25Re |
D |
|
0 .. +2495°C |
0,15% od 500°C |
| W5Re-W26Re |
C |
|
0 .. +2320°C |
0,15% |
| W-W26Re |
G |
|
0 .. +2315°C |
0,15% od 500°C |
| Type tests: |
Basic type test:
EMC:
Safety: |
- in compliance with ČSN EN 60770-1
- in compliance with ČSN EN 61326-1
- in compliance with ČSN EN 61010-1 |
Terminal connection: |
4(-), 5(+):
1(-), 3(+): |
supply 8...28V DC
input
|
|
Dimmension schema: |
| |
 |
Ordering:
In an order is necessary notify:
- type of converter PPL100
- number of pieces
|
Ordering:
In an order is necessary notify: |
| |
- type of converter PX210
- number of pieces
- input signal
thermocouple and it type
direct voltage
direct current |
Order example: |
| |
PX210; 5 pc; Tc J (0..800°C)/4-20mA
PX210; 2 pc; 0..120 mV/4-20mA
PX210; 3 pc; ±10V/4-20mA