Phone: +420 516 416 942, fax: +420 516 416 963, e-mail:


Czech  Czech version  English  English version 

 
 
 
Ikona Page in Acrobat Reader format (120kB)
TRANSMITTER RTD/4...20mA
 
PP200, PP210

PROGRAMMABLE CONVERTER OF TEMPERATURE

Profile:
PP200 PP210
 
Obrázek 01 Obrázek 02

Description:
  - the temperature transmitter PP200 is intended for mounting in the connecting head of the temperature sensor and transmitter PP210 on 35 mm DIN rail.
- simply programming of range by adapter PK-USB without supply (adapter is connect by USB).
- convert temperature from Pt100, Pt1000, Ni100 or Ni1000 sensors to the standard output signal 4-20mA.
- suitable for using in industry enviroment.

Electrical specifications:
- input signal: Pt100, Pt1000 by IEC 751 (–55...640°C)
Ni100, Ni1000 (TKR 5000 and 6180) (-40...230°C)
- programmable range: from 10°C
- accuracy: conformity error: < 0,12°C
  temperature effect: < 0,05°C/10°C
  linearity error: < 0,05% from adjust range (min: 0,1°C for 15 bit and 0,16°C for 14 bit resolurion)
  power supply effect: < 50ppm/V in range (max. 0,2°C)
- resolution input/output: 14 or 15bit/12bit
- input connection: 3 or 2 wire (programmable)
- current limmitation: short circuit on input:       < 3,2mA
  shut off input: > 22,7mA
- the greatest resistor of mains: < 20 W / 1 vodič
- sensor current: < 0,6mA (mean value)
- damping 0...30 s
- sampling period 202 - 810 ms (viz Table 1)
- ambient temperature: -25...+ 80°C
- supply voltage: 8...28V DC
- output signal: 4-20mA
- linear conversion of temperature  
- protection housing / terminal: IP40 / IP10 for DIN rail, IP68 / IP10 for head mounting
- connection: wire from 1,5 to 2,5mm2
- dimensions: see schema
- programmable adapter USB: PK-USB (free programmable software)
     
Type tests:
Basic type test:
EMC:
Safety:
- in compliance with ČSN EN 60770-1
- in compliance with ČSN EN 61326-1
- in compliance with ČSN EN 61010-1

Dimensions and connection of converter:
1, 2:
3:
5(+), 4(-):
temperature resistive sensor (2-wire)
lead of resistive sensor for 3-wire compensation (near the sensor connect with lead nr.2)
current loop 4...20mA

Dimension schema of P200:
 
Obrázek 03

Dimension schema of PP210 (programmable connector is under tab):
 
Obrázek 04
 
Table 1 - sampling period:
  2 wire 3 wire
resolution 14 bit 202 ms 412 ms
resolution 15 bit 404 ms 810 ms

Installation:
   The terminal strips are designed for connecting conductors up to 3.5 mm2 in cross-section. It is recommended to use a cable with a strand cross-section of 1.5 or 2.5 mm2 in accordance with the required resistance of the line.
   The converter PP210 is mounted on the 35 mm DIN rail. The units can operate in any position. They snap onto the rail and are removed without using any other tools.
   PP200 are mounted by screw M4x16 to the connection head of temperature. Leads of sensor be passed through the hole in the center of convertor, then are connected to the terminal.

Ordering:
In an order is necessary notify:
 - type of converter PP200 or PP210
 - number of pieces
 
We can do custom settning, then is necessary notify:
 - type of sensors Pt100, Pt1000, Ni100 or Ni1000 (also TKR)
 - connection of sensor 2W or 3W
 - custom range for instance -10 až 120°C
 - custom damping for instance 0,5s
 - if you don't notify resolution, we set 15 bit