Phone: +420 516 416 942, fax: +420 516 416 963, e-mail:


Czech  Czech version  English  English version 

 
 
 
Ikona Page in Acrobat Reader format (154kB)
AC CONVERTERS
 
Q2S

THREE-WIRE GRID REACTIVE POWER CONVERTER
 
( Aron connection )

Model:
  Q2S  
  Picture 01  

- reactive power in three-wire symmetrical unbalanced grid
- power supply: 24V DC or 230V AC
- frequency range: from 40 to 1000Hz
- input-to-output-to-power supply isolation: 4000Vr.m.s.
- measuring range: 0 to 120% of rated input
- conversion accuracy < 0,5%
- compact design
- designed for DIN 35 rail mounting

      The converter has been designed to convert the reactive power of an AC signal into a unified-range DC voltage or current. The converter input includes measuring current transformers and voltage dividers. These are designed to adjust the input levels for processing in an analog multiplier. The multiplier output signal is proportional to the input instantaneous power. After smoothing out and isolation, it is fed into an output amplifier. The output amplifier generates a DC current or voltage, which is fit for further processing and subsequent evaluation. The current signal may also be conveyed to a larger distance even in a higher interference level environment. Both the input and the output circuit are overload-protected.
      The converter can handle a wide frequency spectrum. It can also be applied to handling distorted waveform input signals. When measuring in a 50Hz-grid, it can process up to the twentieth harmonic of the fundamental frequency.

Electrical specifications:
- operating temperature range: -25...+80°C
- storage temperature range: -40...+ 80°C
- supply voltage: 24V DC± 30%
  230V ± 15%, 50 - 60Hz, max. 2VA
  other options (80..300V DC, 60..250V AC) by arrangement
- protection: resettable thermal cut-out in primary circuit
- rated inputs: 1A, 2,5A, 5A AC
  57,7V, 100V, 110V, 220V, 230V, 380V, 400V, 500V AC
- voltage input current load: 0,5mA
- current input power demand: typically 0,015VA
- input overload capacity: voltage: 2 Unom - 1s
  current:: 2 Inom - 1min, 20 Inom - 1s
- output: 4-20mA, 0-20mA, 0-10V
- output current limit: typically 28mA (electronic cut-out)
- current output maximum load: 15 / Iout (ohm)
- voltage output maximum load: 10mA
- temperature induced error: < 0,02%/°C
- transfer function maximum error: < 0,5%
- transfer function: linear
- test voltage: 4000Vr.m.s.
- output signal settling time: 300ms
- weight: 220g
- enclosure: casing / terminal board: IP40 / IP10
     
Type tests:
Standard type test:
EMC:
Safety:
to CSN EN 60688
to CSN EN 61326-1
assessed acc. to CSN EN 61010-1

Q2S connecting diagram:
 
  Picture 02
Terminal description: 1,2,3,4....input of the phase current to be measured
5,6,7.......input of the delta voltage to be measured
8,9..........output (9 is +)
10,11......auxiliary AC power supply; for DC, 11 is +

Dimension sketch:
 
  Picture 03

Converter capacity: Q = V¯ 3 . Us . If . sin j
Us - delta voltage
If - phase current

Ordering instructions:
Your order should include:
- converter type
- auxiliary supply voltage
- rated input voltage
- rated input current
- measuring range (power)
- output range
- quantity (No. of pieces)