AC CONVERTERS
 
ACP

CONVERTER OF PHASE SHIFT BETWEEN CURRENT AND VOLTAGE
OR TWO GRID VOLTAGES

Model:
  ACP  
  Picture 01  

- zero level crossing method
- the output is a linear function of the phase shift between the inputs
- voltage-to-current, voltage-to-voltage
- frequency range: from 45 to 65Hz
- input-to-output-to-power supply isolation: 4000Vr.m.s.
- measuring range: 20 to 120% of rated input
- conversion accuracy: < 0,5%
- compact design
- designed for DIN 35 rail mounting

      The converter has been designed to convert the magnitude of a phase shift between two voltages of the same frequency into a unified DC voltage or current. Its operation is based on comparing the time difference between the zero point crossing time instants with the duration of the period. The current input is isolated from the voltage input by means of a measuring transformer. After the signal waveform is shaped and the phase difference is calculated, the signal is fed via an isolating optocoupler into the output amplifier. It is converted into an unified output signal. The output is proportional to the phase shift between the inputs. Both the input and the output circuit are overload-protected.
      Owing to the measuring principle used, the converter cannot be applied to heavily distorted waveform voltage or currents.

Electrical specifications:
- operating temperature range: -25...+80°C
- storage temperature range: -40...+ 80°C
- supply voltage: 24V DC± 30%
  230V ± 15%, 50 - 60Hz, max. 2VA
  other options (80..300V DC, 60..250V AC) by arrangement
- protection: resettable thermal cut-out in primary circuit
- rated inputs: 1A, 2,5A, 5A AC
  57,7V, 100V, 110V, 220V, 230V, 380V, 400V, 500V AC
- voltage input current load: 0,5mA
- current input power demand: typically 0,015VA
- input overload capacity: voltage: 2 Unom - 1s
  current: 2 Inom - 1min, 20 Inom - 1s
- standard measuring range    ø: ± 60°
  ± 90°
  ± 120°, other ranges by arrangement
  L2 stands for reference when measuring the phase shift between voltages
- output: 4-20mA, 0-20mA, 0-10V, ± 10V, ± 5mA, ± 20mA
- output current limit: typically 28mA (electronic cut-out)
- current output maximum load: 15 / Iout (ohm)
- voltage output maximum load: 10mA
- transfer function: linear
- transfer function maximum error: < 0,5%
- temperature induced error: < 0,02%/°C
- test voltage: 4000Vr.m.s.
- output signal settling time: 300ms
- weight: 120g
- enclosure: casing / terminal board: IP40 / IP10
     
Type tests:
Standard type test:
EMC:
Safety:
to CSN EN 60688
to CSN EN 61326-1
assessed acc. to CSN EN 61010-1

Terminal designation:
  1,2...input current (second voltage is L2)
3,4...voltage input (first voltage is L1)
5,6...output terminals (6 is +)
7,8...power supply terminals, polarity insensitive
 

Dimension sketch:
 
  Picture 02

Ordering instructions:
Your order should include:
- converter type
- supply voltage
- rated input voltage
- rated input current (second voltage)
- measuring range (phase)
- output range
- quantity (No. of pieces)