Model: |
| |
GY200 |
|
| |
 |
|
- test voltage 4000V input - output
- power transfer to supply a two-wire converter
- low voltage drop in the module, typ. 2,5V
- only 7,5 mm for one channel of separation
- mouting 35mm DIN rail
- transfer accuracy < 0,1% |
The module provides galvanic separation of standard current signals 0-20mA, 4-20mA. The power
for supplying the module is obtained from the input measuring signal. The module can be used to isolate a
two-wire converter supplied by a 4-20mA signal. Galvanic separation is achieved by means of a
transformer. The input DC signal is modulated to an AC signal which, after being transferred by the
transformer, is demodulated back to a DC signal. The input circuit is protected against RFI/EMF and against
incorrect polarity. There is a precise DC transformer in operation principle. Therefore is necessary closed
secondary circuit for primary current passing. |
Specifications: |
| - operating temperature range: |
-25...+70°C |
| - storage temperature range: |
-40...+ 80°C |
| - power supply voltage limit: |
2,5 až 30V |
| - input signal: |
0/4-20mA |
| - transformer ratio: |
1:1 |
| - max. transformation error: |
< 0,1% (load 250ohm) |
| - temperature coefficient: |
< 20ppm / °C |
| - load error: |
< 0,02% for 100 ohm |
| - start current |
< 30uA |
| - test voltage input - output: |
4000Vef |
| - test voltage between channel: |
2 channel 2000 VRMS
3 channel 500 VRMS |
| - time constant: |
c. 1ms for load 250 ohm |
| - weight: |
80, 120, 150g |
| - ambient: |
standard for pollution index 2 and wiring overvoltage category III |
| |
|
|
| Type test: |
Basic type test:
EMC:
Safety: |
-in compliance with ČSN EN 60770-1
-in compliance with ČSN EN 61326-1
-in compliance with ČSN EN 61010-1 |
| |
| Terminal connections: |
| |
input |
output |
| channel A |
1A, 2A ( 2 is + ) |
3A, 4A ( 4 is + ) |
| channel B |
1B, 2B ( 2 is + ) |
3B, 4B ( 4 is + ) |
| channel C |
1C, 2C ( 2 is + ) |
3C, 4C ( 4 is + ) |
Dimension chart:
|
 |
Possible applications of the insulating module:
|
 |
Ordering instructions:
Your purchase order should include the following:
- converter type (after slash number of channel)