Model: |
| |
GX440 |
|
| |
 |
|
- isolation and mutual conversion of 0 to 20mA, 4 to 20mA and 0 to10V signals
- two-wire connection for current signals
- three-wire connection for voltage signals
- isolation electric strength: 4000Vr.m.s.
- very low voltage drop across the current input: max. 2.5V
- DIN 35 rail-mounted design
- conversion accuracy: < 0.2%
- low cost ( no auxiliary power supply is built-in ) |
The module is designed to provide isolation and conversion
of standard range currents and/or voltages, namely, 0 - 20mA, 4 - 20mA and 0 - 10V. The module comprises no
built-in power supply. The converter input and output circuits are therefore powered from the sources of the
voltages/currents fed into the input/output terminals.
The converter current input and output are two-wire connected. The input
circuit is powered from the measured current loop, loading it with a voltage drop of 2.5V at the most. The current
output circuit behaves as a variable resistance. From the external power supply, it is drawing a current which is
directly proportional to the input signal.
The voltage input and output require three-wire connection. Negative terminals
of both the external power supply and the signal circuit are connected to the GND terminal. |
Electrical specifications: |
| - operating temperature range: |
-25...+80°C |
| - storage temperature range: |
-40...+ 80°C |
| - three-wire input supply voltage: |
5...30V DC |
| output: |
12...30V |
| - three-wire input supply current: |
max. 2,5mA |
| output: |
max. 1,5mA |
| - voltage drop across current input: |
max. 2,5V |
| - current output supply voltage: |
3,5...30V DC |
| - transfer function maximum error: |
< 0,2% |
| - temperature induced error: |
< 0,01%/°C |
| - test voltage |
4000Vr.m.s. |
| - input-to-output capacitance: |
10pf |
| - time constant: |
< 0,1s |
| - weight: |
90g |
| |
|
|
| Type tests: |
Standard type test:
EMC:
Safety: |
to ČSN EN 60770-1
to ČSN EN 61326-1
assessed acc. to ČSN EN 61010-1 |
Terminal designation: |
| The terminal connection is apparent from the module application block diagrams. |
Dimension sketch:
|
 |
Isolating module application variants:
|
 |
Ordering instructions:
Your order should include:
- converter type
- input range
- output range
- quantity (No. of pieces)
|
|
|